SPECIFICATIONS | |||||||
Country of Origin | USA | ||||||
Dimension (H x W x L) | 5.0 cm x 10.0 cm x 20.3 cm (1.97 in x 3.94 in x 8.00 in) | ||||||
AC/DC Voltage Measurement | |||||||
Accuracy | Range : 600.0 V Resolution : 0.1 V 50 Hz to 400 Hz ± (% of Rdg + Digits) : ± (2 % + 3) | ||||||
Input impedance | 3 M? (nominal), < 100 pF | ||||||
Common mode rejection ratio (1 k? unbalanced): | > 60 dB at dc, 50 or 60 Hz | ||||||
Overload Protection | 600 V rms or dc | ||||||
Earth bond resistance measurement | |||||||
Range/Resolution | 20.00 ? :0.01 ? 200.0 ? :0.1 ? 2000 ? :1.0 ? 20.00 k? : 0.01 k? | ||||||
Accuracy | ± (1.5 % + 3) | ||||||
Overload Protection | 2 V rms or dc | ||||||
Open Circuit Test Voltage | > 4.0 V, < 8 V | ||||||
Short circuit current | > 200.0 mA | ||||||
Insulation | |||||||
Measurement Range | 1507:00:00 0.01 M? to 10 G? 1503:00:00 0.01 M? to 2000 M? | ||||||
Test voltage | 1507:00:00 50 V, 100 V, 250 V, 500 V, 1000 V 1503:00:00 500 V, 1000V | ||||||
Test Voltage Accuracy | + 20 %, - 0 % | ||||||
Short circuit current | 1 mA nominal | ||||||
Auto Discharge | Discharge time < 0.5 second for C = 1 µF or less | ||||||
Live circuit indicator | Inhibit test if terminal voltage > 30 V prior to initialization of test | ||||||
Maximum Capacitive Load | Operable with up to 1 µF load | ||||||
Measure Accuracy: | 50 V: ±(3 % + 5) 100 V: ±(3 % + 5) 250 V: ±(1.5 % + 5) 500 V: ±(1.5 % + 5) 1000 V: ±(1.5 % + 5) to 2000 M?, ±(10 % + 3) above 2000 M? | ||||||
General | |||||||
Maximum voltage applied to any terminal: | 600 V ac rms or dc | ||||||
Storage Temperature | -40 °C to 60 °C (-40 °F to 140 °F) | ||||||
Operating Temperature | -20 °C to 55 °C (-4 °F to 131 °F) | ||||||
Temperature Coefficient | 0.05 x (specified accuracy) per °C for temperatures < 18 °C or > 28 °C (< 64 °F or > 82 °F) | ||||||
Relative Humidity | 0 % to 95 % @ 10 °C to 30 °C (50 °F to 86 °F) 0 % to 75 % @ 30 °C to 40 °C (86 °F to 104 °F) 0 % to 40 % @ 40 °C to 55 °C (104 °F to 131 °F) | ||||||
Vibration | Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument | ||||||
Shock | 1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor) | ||||||
Electromagnetic compatibility: | In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997) | ||||||
Safety | Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV) | ||||||
Certifications: | CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition | ||||||
Batteries | Four AA batteries (NEDA 15A or IEC LR6) | ||||||
Battery Life | Insulation test use: Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 M? with a duty cycle of 5 seconds on and 25 seconds off. Resistance measurements: Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 ? with a duty cycle of 5 seconds on and 25 seconds off. | ||||||
Weight | 550 g (1.2 lb) | ||||||
IP Rating | IP40 | ||||||
Altitude | Operating: 2000 m CAT IV 600 V, 3000 m CAT III 600 V Non-operating (storage): 12,000 m | ||||||
Over-range capability: | 110 % of range | ||||||
Included accessories: | TL224 Test Leads, TP74 Test Probes, clips PN 1958654 (red) and PN 1958646 (black), holster and remote probe |